Belimo R2025-10-S2 - 2-way ball control valve
Belimo R2025-10-S2 is a 2-way control valve with a control insert for water systems. It has an Rp 1" female threaded connection, DN 25, PN 40 and Kvs 10 m³/h.
Designed for water or water with a maximum of 50% vol. glycol. Medium temperature: -10...120°C [14...248°F].
Belimo R2025-10-S2 – control valve with control insert
2-way valve with a female threaded connection, designed for open and closed water systems and for water-side control in ventilation and heating systems. The integrated control insert provides an equal-percentage flow characteristic.
Key technical data
- Type: R2025-10-S2; DN 25; PN 40; Rp 1" connection.
- Kvs: 10 m³/h; ps: 1600 kPa.
- Medium: water, water with a maximum of 50% vol. glycol.
- Medium temperature: -10...120°C [14...248°F].
- Differential pressure: ∆pmax 350 kPa; closing pressure: 1400 kPa.
- Flow characteristic: equal-percentage; tightness: bubble-tight, class A (EN 12266-1).
- Body: nickel-plated brass; closing element and shaft: stainless steel; control insert: ETFE.
- Rotation angle: 90°; operating range: 15...90°.
Installation instructions
Permitted installation position: from vertical to horizontal relative to the valve axis; do not install with the axis pointing downwards. Observe the direction of flow indicated by the arrow on the body. For medium temperatures of -10...2°C, shaft heating or a valve neck extension is recommended. The permitted temperature range may depend on the actuator used; limitations are specified in its product data sheet. A differential pressure of 200 kPa is specified for quiet operation.
-
Brand
-
ReferenceR2025-10-S2
-
EAN137630498105326
-
Kvs10 m³/h
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern2-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteFor medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
-
Differential pressure∆pmax 350 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Flow characteristicEqual-percentage characteristic
-
Permissible leakageBubble-tight, leakage class A
-
Pipe connectionInternal thread