Belimo R3015-2P5-S1 - 3-way characterised control ball valve
3-way characterised control ball valve for closed water systems. DN 15, PN 40, Rp 1/2" female thread, Kvs 2.5 m³/h.
Designed for continuous control on the water side of ventilation and heating systems. Fluid temperature: -10...120°C [14...248°F].
Belimo R3015-2P5-S1 – 3-way control valve
Characterised control ball valve for closed water systems, designed for continuous control on the water side of ventilation and heating systems.
Key features and specifications
- DN 15, PN 40; Rp 1/2" female thread.
- Kvs 2.5 m³/h; flow through bypass B – AB: 70% of the Kvs value.
- Fluid: water, water with max. 50% by volume glycol; fluid temperature -10...120°C [14...248°F].
- Maximum differential pressure ∆pmax 350 kPa; closing pressure 1400 kPa. 200 kPa is specified to ensure quiet operation.
- Flow characteristic A – AB: equal percentage; B – AB: linear.
- Leakage A – AB: bubble-tight, leakage rate class A; B – AB: leakage rate class I, 1...2% of the Kvs value.
- Nickel-plated brass body; stainless steel closing element and stem.
- Rotary angle: 90°.
Installation notes
Permitted installation position: from vertical to horizontal relative to the axis. Do not install with the axis pointing downwards. Observe the flow direction indicated by the arrow on the body.
At fluid temperatures of -10...2°C, stem heating or a valve neck extension is recommended. The permitted fluid temperature may depend on the actuator used.
-
Brand
-
ReferenceR3015-2P5-S1
-
EAN137630498107191
-
Kvs2.5 m³/h
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern3-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteFor medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
-
Differential pressure∆pmax 350 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Flow characteristicA – AB: equal-percentage; B – AB: linear
-
Permissible leakageA – AB: bubble-tight, leakage class A; B – AB: leakage class I, 1...2% of Kvs value
-
Pipe connectionInternal thread
Over 20 years of experience
Reliable service and customer trust
Help with selecting and operating equipment