Belimo R3025-S2 - 3-way changeover ball valve
Belimo R3025-S2 3-way changeover ball valve for closed water systems. DN 25, Rp 1" female thread, PN 40 and Kvs 26 m³/h.
Designed for changeover and on/off control on the water side of ventilation and heating systems. Medium temperature: -10...120°C [14...248°F].
Belimo R3025-S2 – changeover ball valve
3-way valve for closed water systems, designed for changeover and on/off control on the water side of ventilation and heating systems. The valve is operated by a rotary actuator controlled by an open/close signal.
Key technical data
- DN 25, PN 40; Rp 1" female thread in accordance with ISO 7-1.
- Kvs 26 m³/h; flow through bypass B – AB: approx. 50% of the Kvs value.
- Medium: water or water with max. 50% vol. glycol; medium temperature -10...120°C [14...248°F].
- ∆pmax 1000 kPa; closing pressure ∆ps 1400 kPa. 200 kPa is specified for quiet operation.
- Leakage A – AB: bubble-tight, leakage rate class A (EN 12266-1); B – AB: leakage rate class I (EN 1349 and EN 60534-4), max. 1% of the Kvs value.
- Rotational angle 90°. Nickel-plated brass body; stainless steel closure element and spindle.
- Spindle seal: EPDM O-ring; seat: PTFE, EPDM O-ring.
Installation notes
Installation is permitted from vertical to horizontal in relation to the valve axis; installation with the axis pointing downwards is not permitted. Follow the flow direction indicated by the arrow on the body.
At a medium temperature of -10...2°C, spindle heating or a valve neck extension is recommended. The permitted medium temperature may depend on the actuator type; limitations are specified in the relevant actuator data sheets.
-
Brand
-
ReferenceR3025-S2
-
EAN137630498107764
-
Kvs26 m³/h
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern3-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteFor medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
-
Differential pressure∆pmax 1000 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Permissible leakageA – AB: bubble-tight, leakage class A; B – AB: leakage class I, max. 1% of Kvs value
-
Pipe connectionInternal thread