Belimo R3032-16-S3 - 3-way characterised control ball valve
Belimo R3032-16-S3 3-way characterised control ball valve, DN 32, PN 25, Rp 1 1/4" female thread and Kvs 16 m³/h. Designed for closed water systems and water-side control in ventilation and heating systems.
Medium: water or water with max. 50% vol. glycol. Medium temperature: -10...120°C [14...248°F].
Belimo R3032-16-S3 – 3-way control valve
Valve with characterised control port for closed water systems. Designed for water-side control in ventilation and heating systems. Control is provided by a rotary actuator operated by a modulating or 3-point signal.
Key specifications
- Pattern: 3-way; DN 32; PN 25; ps 1600 kPa.
- Connection: Rp 1 1/4" female thread; Kvs 16 m³/h.
- Medium: water, water with max. 50% vol. glycol; medium temperature: -10...120°C [14...248°F].
- Differential pressure: ∆pmax 350 kPa; closing pressure: 1400 kPa. 200 kPa is indicated for quiet operation.
- Flow characteristic: A – AB equal percentage, B – AB linear; flow through bypass B – AB: 70% of Kvs value.
- Leakage: A – AB bubble-tight, leakage class A; B – AB leakage class I, 1...2% of Kvs value.
- Body: nickel-plated brass; closing element and stem: stainless steel; characterised control port for DN 32: ETFE.
- Angle of rotation: 90°; operating range A – AB: 15...90°, B – AB: 15...70°.
Installation notes
Permitted installation from vertical to horizontal relative to the axis; do not install with the axis pointing downwards. Observe the flow direction marked by the arrow on the body. For medium temperatures of -10...2°C, stem heating or a valve neck extension is recommended. The permissible medium temperature may depend on the actuator type.
-
Brand
-
ReferenceR3032-16-S3
-
EAN137630498107771
-
Kvs16 m³/h
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern3-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteFor medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
-
Differential pressure∆pmax 350 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Flow characteristicA – AB: equal-percentage; B – AB: linear
-
Permissible leakageA – AB: bubble-tight, leakage class A; B – AB: leakage class I, 1...2% of Kvs value
-
Pipe connectionInternal thread
Over 20 years of experience
Reliable service and customer trust
Help with selecting and operating equipment