Belimo R3040-16-S3 - 3-way ball control valve
Belimo R3040-16-S3 is a 3-way control valve with a control orifice for closed water systems. DN 40, PN 25, Rp 1 1/2" female thread and Kvs 16 m³/h.
Designed to regulate flow on the water side of ventilation and heating systems. Medium temperature: -10...120°C [14...248°F].
Belimo R3040-16-S3 – 3-way control valve
A control valve with a control orifice for closed water systems, designed to regulate flow on the water side of ventilation and heating systems. The valve is positioned by a rotary actuator.
Key features and parameters
- Design: 3-way; DN 40; PN 25.
- Connection: Rp 1 1/2" female thread.
- Kvs: 16 m³/h; flow through bypass B – AB: 70% of the Kvs value.
- Medium: water, water with max. 50% vol. glycol; medium temperature: -10...120°C [14...248°F].
- Differential pressure: ∆pmax 350 kPa; closing pressure: 1400 kPa. A differential pressure of 200 kPa is specified for quiet operation.
- Flow characteristic: A – AB equal percentage, B – AB linear.
- Tightness: A – AB bubble-tight, leakage rate class A; B – AB leakage rate class I, 1...2% of the Kvs value.
- Body made of nickel-plated brass; closing element and stem made of stainless steel.
Installation instructions
Permitted mounting position: from vertical to horizontal relative to the valve axis; installation with the axis pointing downwards is not permitted. Observe the flow direction indicated by the arrow on the body.
For medium temperatures of -10...2°C, stem heating or a valve neck extension is recommended. The permitted medium temperature may depend on the actuator type; limitations are specified in the relevant actuator data sheets.
-
Brand
-
ReferenceR3040-16-S3
-
EAN137630498107825
-
Kvs16 m³/h
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern3-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteFor medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
-
Differential pressure∆pmax 350 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Flow characteristicA – AB: equal-percentage; B – AB: linear
-
Permissible leakageA – AB: bubble-tight, leakage class A; B – AB: leakage class I, 1...2% of Kvs value
-
Pipe connectionInternal thread
Over 20 years of experience
Reliable service and customer trust
Help with selecting and operating equipment