Belimo EP065F2-16+BAC - 2-way EPIV control valve DN 65

Price: zł23,629.53
VAT included
zł19,211.00 tax excluded

2-way EPIV control valve with sensor-based, pressure-independent flow control. DN 65 design, PN 16, with flanged connection; V'nom 8.3 l/s (30 m³/h).

AC/DC 24 V supply, 2...10 V control signal and BACnet MS/TP, Modbus RTU and MP-Bus communication. The valve measures fluid temperature and monitors glycol concentration.

Product availability: Product unavailable
Share

Notify me when available

Interested in this product? Drop us an email and we will let you know when it's available for order.

Belimo EP065F2-16+BAC

2-way EPIV control valve with sensor-based flow measurement and control. Designed for closed water systems and water-side control in ventilation and heating systems.

Key features and specifications

  • DN 65, PN 16; flanged connection in accordance with EN 1092-2.
  • Nominal flow V'nom 8.3 l/s (30 m³/h); V'max adjustable within 25...100% V'nom.
  • Fluid: water or water with up to 60% vol. glycol; fluid temperature -10...120°C [14...248°F].
  • Maximum differential pressure ∆pmax 350 kPa; closing pressure ∆ps 690 kPa.
  • AC/DC 24 V supply; power consumption during operation 3.3 W, in standby position 2.4 W; 6.2 VA for cable sizing.
  • Y control signal 2...10 V; BACnet MS/TP, Modbus RTU and MP-Bus communication. Hybrid mode available.
  • Ultrasonic flow measurement, fluid temperature measurement and glycol concentration monitoring 0...60%.
  • NFC interface for configuration and operation using Belimo Assistant 2; manual adjustment by push-button, with option to lock.
  • 1 m power and control cable, 6x 0.75 mm²; IEC/EN IP54 protection rating; IEC/EN protection class III, Protective Extra-Low Voltage (PELV).

For fluid temperatures of -10...2°C, extending the valve neck is recommended. The permissible fluid temperature range may depend on the actuator type.

  • Brand
  • Reference
    EP065F2-16+BAC
  • EAN13
    7630498136771

  • Medium
    Water, water with max. 60% vol. glycol.
  • Pattern
    2-way
  • Fluid temperature
    -10...120°C [14...248°F]
  • Fluid temperature, note
    At a fluid temperature of -10...2°C, extending the valve neck is recommended. The permissible fluid temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for limitations.
  • Differential pressure
    ∆pmax 350 kPa
  • Closing pressure
    690 kPa
  • Differential pressure note
    200 kPa for quiet operation
  • Flow characteristic
    Equal-percentage characteristic
  • Permissible leakage
    Bubble-tight, leakage class A
  • Pipe connection
    Flange
  • V'nom [l/s]
    8.3
  • Adjustable flow rate
    25...100% V'nom

Techniczna karta katalogowa

Download (3.95MB)

Instrukcja montażu

Download (979.51KB)

Techniczna karta katalogowa – EP..F2-16+BAC

Download (3.96MB)

EU Declaration of Conformity – EP065F2-16+BAC

Download (361.77KB)
In business since 2005
Over 20 years of experience
A trusted partner
Reliable service and customer trust
Technical support
Help with selecting and operating equipment

You might also like

Comments (0)

No customer reviews for the moment.

4 other products in the same category

Loading...
Back to top