Belimo R423 - 2-way control valve with orifice
Belimo R423 is a 2-way control valve with orifice, DN 25, PN 40, with G 1 1/2" male thread and Kvs 10 m³/h. It is designed for water-side control in ventilation and heating systems.
Medium temperature is -10...100°C [14...212°F]. The valve has an equal-percentage characteristic and leakage class A.
Belimo R423 – control valve with orifice
2-way valve for open and closed water systems and water-side control in ventilation and heating systems. The integrated control orifice provides an equal-percentage flow characteristic.
Key features
- DN 25, PN 40; G 1 1/2" male thread.
- Kvs 10 m³/h; ps 1600 kPa.
- Medium: water or water with max. 50% vol. glycol.
- Medium temperature: -10...100°C [14...212°F].
- Differential pressure: ∆pmax 200 kPa; closing pressure: 1400 kPa.
- Flow characteristic: equal-percentage; leakage: bubble-tight, leakage class A.
- Nickel-plated brass body; stainless steel closing element and stem.
- Pipe connection: male thread according to ISO 228-1.
For medium temperatures of -10...2°C, a valve neck extension is recommended. The permitted medium temperature may depend on the actuator type; limitations are specified in the relevant actuator data sheets.
Permitted mounting position: from vertical to horizontal in relation to the stem. Do not install with the stem pointing downwards.
-
Brand
-
ReferenceR423
-
EAN137630498108150
-
Kvs10 m³/h
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern2-way
-
Fluid temperature-10...100°C [14...212°F]
-
Fluid temperature, noteAt a fluid temperature of -10...2°C, extending the valve neck is recommended. The permissible fluid temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for limitations.
-
Differential pressure∆pmax 200 kPa
-
Closing pressure1400 kPa
-
Flow characteristicEqual-percentage characteristic
-
Permissible leakageBubble-tight, leakage class A
-
Pipe connectionExternal thread