Belimo R511 is a 3-way ball control valve with a regulating orifice, DN 15, PN 40, with G 1" external thread. The Kvs value is 1.6 m³/h, and the fluid temperature is -10...100°C [14...212°F].

Designed for water-side control in ventilation and heating systems, in open and closed water circuits.

Product availability: Delivery in approx. 14 days
Share

Belimo R511 – 3-way control valve

Ball valve with a regulating orifice for modulating water-side flow control in ventilation and heating systems. The valve is operated by a rotary actuator; the actuator is not specified as part of the set.

Key features and specifications

  • Pattern: 3-way; DN 15; PN 40.
  • Connection: G 1" external thread according to ISO 228-1.
  • Kvs: 1.6 m³/h; flow through bypass B – AB: 70% of the Kvs value.
  • Medium: water, water with up to 50% vol. glycol.
  • Fluid temperature: -10...100°C [14...212°F].
  • Differential pressure: ∆pmax 200 kPa; closing pressure: 1400 kPa.
  • Flow characteristic: A – AB equal percentage, B – AB linear.
  • Leakage: A – AB bubble-tight, leakage class A; B – AB leakage class I, 1...2% of the Kvs value.
  • Body: nickel-plated brass; closing element and stem: stainless steel; regulating orifice: ETFE.
  • Rotation angle: 90°.

Installation notes

Permitted mounting position: from vertical to horizontal relative to the stem; do not install with the stem pointing downwards. At a fluid temperature of -10...2°C, extending the valve neck is recommended. The permitted fluid temperature may depend on the actuator used.

  • Brand
  • Reference
    R511
  • EAN13
    7630498108327

  • Kvs
    1.6 m³/h
  • Medium
    Water, water with up to 50% vol. glycol.
  • Pattern
    3-way
  • Fluid temperature
    -10...100°C [14...212°F]
  • Fluid temperature, note
    At a fluid temperature of -10...2°C, extending the valve neck is recommended. The permissible fluid temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for limitations.
  • Differential pressure
    ∆pmax 200 kPa
  • Closing pressure
    1400 kPa
  • Flow characteristic
    A – AB: equal-percentage; B – AB: linear
  • Permissible leakage
    A – AB: bubble-tight, leakage class A; B – AB: leakage class I, 1...2% of Kvs value
  • Pipe connection
    External thread

Techniczna karta katalogowa

Download (799.15KB)

Instrukcja montażu

Download (556.22KB)

Techniczna karta katalogowa – R5.. modulating

Download (801.12KB)

EU Declaration of Conformity – R5.. / R4.. DN 15...50

Download (55.18KB)

Environmental Declaration – R5..

Download (70.42KB)
In business since 2005
Over 20 years of experience
A trusted partner
Reliable service and customer trust
Technical support
Help with selecting and operating equipment

You might also like

Comments (0)

No customer reviews for the moment.

4 other products in the same category

Loading...
Back to top