Belimo EP125F2-16+KBAC - 2-way EPIV control valve

Price: zł51,886.32
VAT included
zł42,184.00 tax excluded

2-way EPIV control valve with pressure-independent flow measurement and control, and a safety function. DN 125, PN 16, flanged connection, V'nom 33.3 l/s.

AC/DC 24 V supply; 2...10 V control and BACnet MS/TP, Modbus RTU and MP-Bus communication. Intended for closed water systems.

Product availability: Product unavailable
Share

Notify me when available

Interested in this product? Drop us an email and we will let you know when it's available for order.

Belimo EP125F2-16+KBAC

2-way EPIV control valve with sensor-based flow measurement and a safety function. Intended for water-side control in ventilation and heating systems in closed water circuits.

Key features and specifications

  • DN 125, PN 16; flanged connection.
  • V'nom 33.3 l/s (120 m³/h); V'max setting 25...100% V'nom.
  • Medium: water or water with a maximum of 60% by volume glycol; medium temperature -10...120°C [14...248°F].
  • Differential pressure ∆pmax 350 kPa; closing pressure ∆ps 690 kPa.
  • AC/DC 24 V supply; power consumption during operation 12.1 W, at rest 4.1 W.
  • Operating range Y 2...10 V; modulating, communicative and hybrid control; BACnet MS/TP, Modbus RTU, MP-Bus.
  • Safety function stroke time 35 s / 90°; safety position NC/NO or adjustable 0...100%.
  • Ultrasonic flow measurement, medium temperature measurement and glycol concentration monitoring 0...60%.
  • NFC interface for configuration via Belimo Assistant 2; manual override by push-button.
  • Degree of protection IEC/EN IP54; protection class IEC/EN III, Protective Extra-Low Voltage (PELV).

For medium temperatures of -10...2°C, extending the valve neck is recommended. The permissible medium temperature may depend on the actuator used.

  • Brand
  • Reference
    EP125F2-16+KBAC
  • EAN13
    7630498136900

  • Medium
    Water, water with max. 60% vol. glycol.
  • Pattern
    2-way
  • Fluid temperature
    -10...120°C [14...248°F]
  • Fluid temperature, note
    At a fluid temperature of -10...2°C, extending the valve neck is recommended. The permissible fluid temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for limitations.
  • Differential pressure
    ∆pmax 350 kPa
  • Closing pressure
    690 kPa
  • Differential pressure note
    200 kPa for quiet operation
  • Flow characteristic
    Equal-percentage characteristic
  • Permissible leakage
    Bubble-tight, leakage class A
  • Pipe connection
    Flange
  • V'nom [l/s]
    33.3
  • Adjustable flow rate
    25...100% V'nom

Techniczna karta katalogowa

Download (4.29MB)

Instrukcja montażu

Download (1007.6KB)

Techniczna karta katalogowa – EP..F2-16+KBAC

Download (4.26MB)

EU Declaration of Conformity – EP125F2-16+KBAC

Download (361.78KB)
In business since 2005
Over 20 years of experience
A trusted partner
Reliable service and customer trust
Technical support
Help with selecting and operating equipment

You might also like

Comments (0)

No customer reviews for the moment.

4 other products in the same category

Loading...
Back to top