Belimo R530 - 3-way changeover ball valve
Belimo R530 is a DN 32 3-way changeover ball valve with G 2" male thread, PN 40 and Kvs 16 m³/h. It is designed for changeover and open/close control functions on the water side of ventilation and heating systems.
Medium: water or water with max. 50% vol. glycol; medium temperature -10...100°C [14...212°F].
Belimo R530 – changeover ball valve
3-way ball valve with male thread, designed for open and closed water systems. It can be used for changeover and open/close control functions on the water side of ventilation and heating systems.
Key technical data
- Type: R530; DN 32; G 2" male thread in accordance with ISO 228-1.
- PN 40; ps 1600 kPa; Kvs 16 m³/h.
- Medium: water, water with max. 50% vol. glycol; potable water on request.
- Medium temperature: -10...100°C [14...212°F].
- Differential pressure: ∆pmax 400 kPa; closing pressure: 1400 kPa. 200 kPa is specified for quiet operation.
- Flow through bypass B – AB: approx. 50% of the Kvs value.
- Tightness A – AB: bubble-tight, leakage class A (EN 12266-1); B – AB: leakage class I (EN 1349 and EN 60534-4), max. 1% of the Kvs value.
- Rotation angle: 90°. Nickel-plated brass body; stainless steel closing element and stem.
Installation notes
Permitted installation position: from vertical to horizontal in relation to the stem; installation with the stem pointing downwards is not permitted. Observe the flow direction indicated by the arrow on the body.
For a medium temperature of -10...2°C, a valve neck extension is recommended. The permitted medium temperature may depend on the actuator type; limitations are stated in the relevant actuator data sheets.
-
Brand
-
ReferenceR530
-
EAN137630498108433
-
Kvs16 m³/h
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern3-way
-
Fluid temperature-10...100°C [14...212°F]
-
Fluid temperature, noteAt a fluid temperature of -10...2°C, extending the valve neck is recommended. The permissible fluid temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for limitations.
-
Differential pressure∆pmax 400 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Permissible leakageA – AB: bubble-tight, leakage class A; B – AB: leakage class I, max. 1% of Kvs value
-
Pipe connectionExternal thread