Belimo R6040R-B3 - 2-way open/close ball valve

Price: zł1,338.86
VAT included
zł1,088.50 tax excluded

Belimo R6040R-B3 is a 2-way open/close ball valve with flanged connection, DN 40, PN 6 and Kvs 31 m³/h. Designed for open and closed water systems.

Suitable for water and water with up to 50% vol. glycol. Fluid temperature: -10...100°C [14...212°F]; closing pressure: 600 kPa.

Product availability: Delivery in approx. 14 days
Share

Belimo R6040R-B3 – 2-way ball valve

Open/close valve for water-side shut-off functions and open/close control in ventilation and heating systems. It is designed for open and closed water systems. Control is provided by a rotary actuator operated by an open/close signal.

Key features and specifications

  • Type: 2-way; DN 40; PN 6.
  • Pipe connection: flange to EN 1092-1/4.
  • Kvs: 31 m³/h.
  • Fluid: water, water with up to 50% vol. glycol.
  • Fluid temperature: -10...100°C [14...212°F].
  • Closing pressure ∆ps: 600 kPa; differential pressure Δpmax: 100 kPa.
  • Tightness: bubble-tight, leakage rate class A (EN 12266-1).
  • Rotation angle: 90°. The valve opens by turning anticlockwise and closes by turning clockwise.
  • Body: nickel-plated brass; closing element: chrome-plated brass; flange for DN 40: aluminium.

Installation notes

Permitted mounting position: from vertical to horizontal relative to the valve axis. Do not install with the axis pointing downwards. Observe the flow direction indicated by the arrow on the body.

For fluid temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permitted fluid temperature may be limited depending on the actuator type; limitations are stated in the relevant actuator datasheets.

  • Brand
  • Reference
    R6040R-B3
  • EAN13
    7630498108600

  • Kvs
    31 m³/h
  • Medium
    Water, water with up to 50% vol. glycol.
  • Pattern
    2-way
  • Fluid temperature
    -10...100°C [14...212°F]
  • Fluid temperature, note
    For medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
  • Differential pressure
    ∆pmax 100 kPa
  • Closing pressure
    600 kPa
  • Permissible leakage
    Bubble-tight, leakage class A
  • Pipe connection
    Flange

Techniczna karta katalogowa

Download (1.18MB)

Instrukcja montażu

Download (507.05KB)

Techniczna karta katalogowa – R6..R-B..

Download (1.18MB)

EU Declaration of Conformity – R20.., R30.., R60..R.., R70..R.., DN15...50

Download (64.14KB)

Environmental Declaration – R6.. DN15-50

Download (70.21KB)
In business since 2005
Over 20 years of experience
A trusted partner
Reliable service and customer trust
Technical support
Help with selecting and operating equipment

You might also like

Comments (0)

No customer reviews for the moment.

4 other products in the same category

Loading...
Back to top