Belimo R7050R-B3 - 3-way changeover ball valve DN 50

Price: zł1,958.25
VAT included
zł1,592.07 tax excluded

Belimo R7050R-B3 3-way changeover ball valve with PN 6 flange connection. Specifications: DN 50, Kvs 49 m³/h, fluid temperature -10...100°C [14...212°F].

Designed for closed water systems and changeover and open/close control functions on the water side of ventilation and heating systems.

Product availability: Delivery in approx. 14 days
Share

Belimo R7050R-B3 – changeover ball valve

3-way valve with a flange connection, designed for closed water systems. Suitable for water or water with a maximum of 50% vol. glycol.

Key specifications

  • Nominal size: DN 50; nominal pressure: PN 6.
  • Kvs: 49 m³/h; flow through bypass B – AB: approx. 50% of the Kvs value.
  • Fluid temperature: -10...100°C [14...212°F].
  • Differential pressure: ∆pmax 100 kPa; closing pressure: 600 kPa.
  • Tightness A – AB: bubble-tight, leakage rate class A (EN 12266-1); B – AB: leakage rate class I (EN 1349 and EN 60534-4), max. 1% of the Kvs value.
  • Rotation angle: 90°; pipe connection: flange according to EN 1092-1/4.
  • Body: nickel-plated brass; flange for DN 50: aluminium.

Installation notes

Permitted mounting position: from vertical to horizontal relative to the axis. Do not install with the axis pointing downwards. For fluid temperatures of -10...2°C, heating the shaft or using a valve neck extension is recommended. The permitted fluid temperature range may depend on the actuator type.

  • Brand
  • Reference
    R7050R-B3
  • EAN13
    7630498108815

  • Kvs
    49 m³/h
  • Medium
    Water, water with up to 50% vol. glycol.
  • Pattern
    3-way
  • Fluid temperature
    -10...100°C [14...212°F]
  • Fluid temperature, note
    For medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
  • Differential pressure
    ∆pmax 100 kPa
  • Closing pressure
    600 kPa
  • Permissible leakage
    A – AB: bubble-tight, leakage class A; B – AB: leakage class I, max. 1% of Kvs value
  • Pipe connection
    Flange

Techniczna karta katalogowa

Download (1.34MB)

Instrukcja montażu

Download (342.98KB)

Techniczna karta katalogowa – R7..R-B..

Download (1.34MB)

EU Declaration of Conformity – R20.., R30.., R60..R.., R70..R.., DN15...50

Download (64.14KB)

Environmental Declaration – R7..

Download (71.65KB)
In business since 2005
Over 20 years of experience
A trusted partner
Reliable service and customer trust
Technical support
Help with selecting and operating equipment

You might also like

Comments (0)

No customer reviews for the moment.

4 other products in the same category

Loading...
Back to top