Belimo X8042M.3BA23 - 2-way control valve for refrigerants
Belimo X8042M.3BA23 2-way control valve for regulating refrigerant flow. Kvs 8 m³/h, connection with internal ODF 42-42 mm soldering socket and permissible operating pressure ps 5000 kPa.
Suitable for A3 safety class refrigerants (ISO 817) as well as CFC, HFC, HFO and R290. Modulating control AC/DC 24 V; emergency closing with SuperCap.
Belimo X8042M.3BA23 – control valve
2-way control valve with an equal-percentage characteristic, designed to regulate refrigerant flow. The rotary actuator controls the valve, while the SuperCap function enables emergency closing.
Key technical data
- Kvs: 8 m³/h; connection: internal ODF 42-42 mm soldering socket.
- Permissible operating pressure ps: 5000 kPa; maximum differential pressure ∆pmax: 3500 kPa.
- Modulating control; rated voltage AC/DC 24 V; operating range Y: 0.5...10 V; position feedback signal U: 0.5...10 V.
- Motor and emergency function operating time: 15 s / 90°; power consumption during operation: 2.5 W, in standby position: 0.5 W.
- Medium temperature: -20...70°C [-4...158°F]; with ZCQ-E: 70...120°C [158...248°F]. Ambient temperature: -30...50°C [-22...122°F], without radiation.
- Tightness: no air bubbles, leakage rate class A (EN 12266-1); flow characteristic: equal percentage (VDI/VDE 2173).
- Body: CW617N brass; closing element: AISI 316L stainless steel.
- IEC/EN degree of protection IP40; IEC/EN protection class III, Safety Extra-Low Voltage (SELV).
- Power and control cable: 3 m, 4x 0.34 mm².
Installation from vertical to horizontal orientation relative to the spindle; installation with the spindle pointing downwards is not permitted. Flow is possible in both directions. When using flammable refrigerants, the user must verify the product’s suitability for the specific installation.
-