Belimo C220QFL-H - 2-way PI flow limiter valve
Belimo C220QFL-H is a 2-way PI flow limiter valve (PIFLV) for closed water systems. It has an Rp 3/4" female thread connection, DN 20, PN 25 and a nominal flow rate V'nom 2900 l/h.
The integrated flow limiter maintains a constant flow rate at a differential pressure of 20...280 kPa. Fluid temperature: 2...60°C [36...140°F].
Belimo C220QFL-H – PI flow limiter valve
The 2-way PIFLV ball valve is designed for closed water systems, including on/off control on the water side of fan coil units and chilled ceilings. The integrated flow limiter maintains a constant flow rate at a differential pressure of 20...280 kPa when the valve is open at an angle of 90°.
Key features
- Size: DN 20; connection: Rp 3/4" female thread; PN 25.
- Nominal flow rate V'nom: 2900 l/h (0.81 l/s).
- Fluid: water; fluid temperature: 2...60°C [36...140°F].
- Differential pressure: 20...280 kPa; closing pressure ∆ps: 520 kPa.
- Tightness: bubble-tight, leakage rate class A (EN 12266-1).
- Body and stem: brass; closing element: chrome-plated brass.
- Rotation angle: 90°; the valve opens counterclockwise and closes clockwise.
Installation notes
Permitted mounting position: from vertical to horizontal in relation to the stem; installation with the stem pointing downwards is not permitted. Observe the flow direction indicated by the arrow on the body. The manufacturer recommends installation on the return and the use of a suitable strainer. A differential pressure of 50 kPa is specified for quiet operation.
-
Brand
-
ReferenceC220QFL-H
-
EAN137630498119187
-
V'nom [l/h]2900
-
MediumWater
-
Pattern2-way
-
Fluid temperature2...60°C [36...140°F]
-
Differential pressure∆p 20...280 kPa
-
Closing pressure520 kPa
-
Differential pressure note50 kPa to ensure quiet operation
-
Permissible leakageBubble-tight, leakage class A
-
Pipe connectionInternal thread
-
V'nom [l/s]0.81
Over 20 years of experience
Reliable service and customer trust
Help with selecting and operating equipment