Belimo H713N - 3-way globe valve DN 15
Belimo H713N is a 3-way globe valve with flanged connection, DN 15, PN 16 and Kvs 1.6 m³/h. Designed for closed water systems and water-side control in ventilation and heating systems.
Fluid: water or water with up to 50% by volume glycol; fluid temperature -10...120°C [14...248°F].
Belimo H713N – 3-way globe valve
Flanged valve for closed water systems, designed for water-side control in ventilation and heating systems.
Key parameters
- DN 15, PN 16, Kvs 1.6 m³/h; stroke 15 mm.
- Fluid: water or water with up to 50% by volume glycol; fluid temperature -10...120°C [14...248°F].
- Flow characteristic: A – AB equal-percentage, B – AB linear.
- Permissible leakage: A – AB max. 0.05% of Kvs value; B – AB max. 1% of Kvs value.
- Body: EN-GJL-250 (GG 25); plug and stem in stainless steel; stem seal: EPDM O-ring.
- Flanged connection in accordance with ISO 7005-2.
Installation notes
Installation is permitted from the vertical to the horizontal position relative to the valve axis; installation with the stem pointing downwards is not permitted. Observe the flow direction indicated by the arrow on the body. For fluid temperatures of -10...2°C, the technical data sheet indicates that stem heating is required.
-
Brand
-
ReferenceH713N
-
EAN137630498106637
-
Kvs1.6 m³/h
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern3-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteWhen the medium temperature is -10...2°C, shaft heating is recommended.
-
Flow characteristicA – AB: equal-percentage; B – AB: linear
-
Permissible leakageA – AB: max. 0.05% of Kvs value; B – AB: max. 1% of Kvs value
-
Pipe connectionFlange
Over 20 years of experience
Reliable service and customer trust
Help with selecting and operating equipment