Belimo R2015-2P5-S1 - 2-way modulating ball valve
2-way modulating valve with Belimo R2015-2P5-S1 characteristic disk for water-side flow control in ventilation and heating systems. DN 15, Rp 1/2" female thread, PN 40, Kvs 2.5 m³/h.
Suitable for water and water with up to 50% vol. glycol; fluid temperature -10...120°C [14...248°F].
Belimo R2015-2P5-S1 – 2-way modulating valve
Valve with characteristic disk for water-side flow control in ventilation and heating systems, in open and closed water circuits. The integrated disk provides an equal-percentage flow characteristic. The valve is operated by a rotary actuator.
Key features and specifications
- DN 15; connection: Rp 1/2" female thread in accordance with ISO 7-1; PN 40.
- Kvs 2.5 m³/h; ps 1600 kPa.
- Fluid: water, water with up to 50% vol. glycol; fluid temperature -10...120°C [14...248°F].
- Differential pressure: ∆pmax 350 kPa; closing pressure: 1400 kPa. For quiet operation: 200 kPa.
- Flow characteristic: equal-percentage; leakage: bubble-tight, leakage rate A (EN 12266-1).
- Nickel-plated brass body; stainless steel closing element and stem; ETFE characteristic disk.
- Rotation angle 90°; operating range 15...90°.
Installation notes
Permitted installation position: from vertical to horizontal relative to the axis; do not install with the axis pointing downwards. Observe the flow direction indicated by the arrow on the body. For fluid temperatures of -10...2°C, stem heating or a valve neck extension is recommended. The permitted fluid temperature range may depend on the actuator used.
-
Brand
-
ReferenceR2015-2P5-S1
-
EAN137630498105210
-
Kvs2.5 m³/h
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern2-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteFor medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
-
Differential pressure∆pmax 350 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Flow characteristicEqual-percentage characteristic
-
Permissible leakageBubble-tight, leakage class A
-
Pipe connectionInternal thread
Over 20 years of experience
Reliable service and customer trust
Help with selecting and operating equipment