Belimo R3015-BL1 - 3-way changeover ball valve
Belimo R3015-BL1 is a 3-way changeover ball valve with an L-shaped bore. It has an Rp 1/2" female threaded connection, DN 15, PN 40 and Kvs 5.5 m³/h.
Designed for water and water with a maximum of 50% vol. glycol; fluid temperature is -10...100°C [14...212°F].
Belimo R3015-BL1 changeover ball valve
3-way valve with an L-shaped bore, designed for changeover and open/close control on the water side of ventilation and heating systems. The valve is positioned by a rotary actuator controlled by an open/close signal.
Main features and specifications
- DN 15, PN 40; Rp 1/2" female thread in accordance with ISO 7-1.
- Kvs 5.5 m³/h; ps 1600 kPa.
- Medium: water, water with a maximum of 50% vol. glycol.
- Fluid temperature: -10...100°C [14...212°F].
- Differential pressure: ∆pmax 350 kPa; closing pressure ∆ps 500 kPa. 200 kPa is specified for quiet operation.
- Tightness: bubble-tight, leakage rate A (EN 12266-1).
- Rotation angle: 90°.
- Nickel-plated brass body; chrome-plated brass closing element; spindle seal: EPDM O-ring.
Installation notes
Permitted installation position: from vertical to horizontal relative to the axis. Do not install with the axis pointing downwards. For fluid temperatures of -10...2°C, spindle heating or a valve neck extension is recommended. The permitted fluid temperature may depend on the actuator type; limitations are specified in the relevant actuator data sheets.
-
Brand
-
ReferenceR3015-BL1
-
EAN137630498107214
-
Kvs5.5 m³/h
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern3-way
-
Fluid temperature-10...100°C [14...212°F]
-
Fluid temperature, noteFor medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
-
Differential pressure∆pmax 350 kPa
-
Closing pressure500 kPa
-
Differential pressure note200 kPa for quiet operation
-
Permissible leakageBubble-tight, leakage class A
-
Pipe connectionInternal thread