Belimo R3015-P63-P4-B1 - 6-way control valve with characterized insert
6-way control valve with characterized insert for closed water systems, designed for switching or controlling the water side of heating and cooling units. DN 15, PN 16, Rp 1/2" female thread; Kvs (sequence 1) 0.63 m³/h and Kvs (sequence 2) 0.4 m³/h.
Controls two sequences using a rotary actuator with a 90° rotation angle. It has a dead zone between sequences and an integrated function that compensates for pressure changes when the valve is closed.
Belimo R3015-P63-P4-B1
6-way control valve with characterized insert for closed water systems. It enables switching or controlling the water flow through heating and cooling units. The two sequences are set using a rotary actuator.
Key features and parameters
- DN 15, PN 16; Rp 1/2" female-thread connection.
- Kvs (sequence 1): 0.63 m³/h; Kvs (sequence 2): 0.4 m³/h.
- Medium: water or water with a maximum of 50% vol. glycol; medium temperature 6...80°C [43...176°F].
- Maximum differential pressure ∆pmax 100 kPa; closing pressure 350 kPa. Quiet operation condition: Δpv100 <50 kPa.
- Linear flow characteristic; bubble-tight, leakage class A (EN 12266-1).
- 90° rotation angle: sequence 1 from 0...30° (recommended for cooling), dead zone 30...60°, sequence 2 from 60...90° (recommended for heating).
- The integrated function compensating for changes in medium pressure operates in the closed position (45°), while keeping the sequences separated.
- Nickel-plated brass body; chrome-plated brass closing element.
Installation notes
Installation is permitted from vertical to horizontal in relation to the stem. Do not install with the stem pointing downwards. Observe the flow direction; the ball position is indicated by the L marking on the stem.
-
Brand
-
ReferenceR3015-P63-P4-B1
-
EAN137630498107443
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern6-way
-
Fluid temperature6...80°C [43...176°F]
-
Differential pressure∆pmax 100 kPa
-
Closing pressure350 kPa
-
Differential pressure notequiet operation Δpv100 <50 kPa
-
Flow characteristicLinear
-
Permissible leakageBubble-tight, leakage class A
-
Pipe connectionInternal thread
-
Kvs (sequence 1)0.63 m³/h
-
Kvs (sequence 2)0.4 m³/h
Over 20 years of experience
Reliable service and customer trust
Help with selecting and operating equipment