Belimo EXT-H625XP-400 - pressure-independent 2-way globe valve
Belimo EXT-H625XP-400 is a 2-way globe valve with flow independent of pressure changes, DN 25, PN 25, with a flange connection. The nominal flow V'nom is 1.1 l/s.
Designed for closed water circuits (pH >7) and district heating networks. Medium temperature: 5...140°C [41...284°F].
Belimo EXT-H625XP-400 globe valve
2-way globe valve with a mechanical differential pressure regulator and a control valve driven by a Belimo actuator. The regulator compensates for pressure fluctuations, maintaining a constant differential pressure across the control valve. Correct flow control requires the minimum differential pressure across the valve to be maintained.
Key technical data
- Nominal diameter: DN 25; nominal pressure: PN 25.
- Connection: flange in accordance with EN 1092-2.
- Nominal flow V'nom: 1.1 l/s (4 m³/h).
- Theoretical Kvs value: 8 m³/h; stroke: 11 mm.
- Medium: water, water with up to 30% vol. glycol.
- Medium temperature: 5...140°C [41...284°F].
- Maximum differential pressure across the control valve: 1500 kPa.
- Flow characteristic: equal percentage.
- Permissible leakage for DN 25: max. 0.02% of the Kvs value.
- Body: EN-GJS-400-18-LT (GGG 40.3).
Application and installation
The valve is designed for closed water circuits (pH >7) and district heating networks. Permissible mounting position: vertical to ±45° relative to the stem. Observe the direction of flow indicated by the arrow on the body.
To prevent cavitation during operation, the maximum differential pressure ∆pmax must be calculated in accordance with the design notes.
-
Brand
-
ReferenceEXT-H625XP-400
-
EAN137630498120343
-
MediumWater, water with max. 30% vol. glycol.
-
Pattern2-way
-
Fluid temperature5...140°C [41...284°F]
-
Differential pressure noteTo prevent cavitation during operation, the maximum differential pressure ∆pmax must be calculated in accordance with the design notes.
-
Flow characteristicEqual-percentage characteristic
-
Permissible leakageMax. 0.02% of Kvs value
-
Pipe connectionFlange
-
V'nom [l/s]1.1
Over 20 years of experience
Reliable service and customer trust
Help with selecting and operating equipment