Belimo R3015-S1 - 3-way changeover ball valve DN 15
Belimo R3015-S1 is a 3-way changeover ball valve for closed water systems, designed for changeover and open/close control on the water side of ventilation and heating systems.
Rp 1/2" female thread, Kvs 15 m³/h, PN 40. Permitted medium: water or water with a maximum of 50% vol. glycol; medium temperature -10...120°C [14...248°F].
Belimo R3015-S1 changeover ball valve
3-way valve for closed water systems. Designed for changeover and open/close control on the water side of ventilation and heating systems. The valve is operated by a rotary actuator controlled by an open/close signal.
Key features and specifications
- DN 15, PN 40; Rp 1/2" female threaded connection in accordance with ISO 7-1.
- Kvs 15 m³/h; flow through bypass B – AB: approx. 50% of the Kvs value.
- Medium: water or water with a maximum of 50% vol. glycol; medium temperature -10...120°C [14...248°F].
- Maximum differential pressure Δpmax 1000 kPa; closing pressure ∆ps 1400 kPa. 200 kPa is specified for quiet operation.
- Tightness A – AB: bubble-tight, leakage class A (EN 12266-1); B – AB: leakage class I (EN 1349 and EN 60534-4), max. 1% of the Kvs value.
- Rotation angle 90°. Nickel-plated brass body; stainless steel closure element and stem.
- Stem seal: EPDM O-ring; seat: PTFE, EPDM O-ring.
Installation notes
Permitted mounting position: from vertical to horizontal relative to the stem; do not install with the stem pointing downwards. Observe the flow direction indicated by the arrow on the body. For medium temperatures of -10...2°C, heating the shaft or using a valve neck extension is recommended. The permitted medium temperature may depend on the actuator type; refer to its product data sheet for limitations.
-
Brand
-
ReferenceR3015-S1
-
EAN137630498107498
-
Kvs15 m³/h
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern3-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteFor medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
-
Differential pressure∆pmax 1000 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Permissible leakageA – AB: bubble-tight, leakage class A; B – AB: leakage class I, max. 1% of Kvs value
-
Pipe connectionInternal thread
Over 20 years of experience
Reliable service and customer trust
Help with selecting and operating equipment