Belimo R3020-4-S2 - 3-way ball control valve
Belimo R3020-4-S2 is a 3-way control valve with a regulating orifice for closed water systems. DN 20, PN 40, Rp 3/4" female thread and Kvs 4 m³/h.
Designed to regulate flow on the water side of ventilation and heating systems. Medium: water or water with max. 50% vol. glycol; medium temperature -10...120°C [14...248°F].
Belimo R3020-4-S2 – 3-way control valve
A valve with a regulating orifice for closed water systems, designed for water-side control in ventilation and heating systems. Control is provided by a rotary actuator operated by a modulating or 3-point signal.
Key features and parameters
- Pattern: 3-way; DN 20; PN 40.
- Connection: Rp 3/4" female thread.
- Kvs: 4 m³/h; flow through bypass B – AB: 70% of the Kvs value.
- Medium: water, water with max. 50% vol. glycol.
- Medium temperature: -10...120°C [14...248°F].
- Differential pressure: ∆pmax 350 kPa; closing pressure: 1400 kPa. 200 kPa is specified for quiet operation.
- Flow characteristic: A – AB equal percentage, B – AB linear.
- Leakage: A – AB bubble-tight, leakage class A; B – AB leakage class I, 1...2% of the Kvs value.
- Nickel-plated brass body; stainless steel closing element and stem.
- Rotation angle: 90°.
For medium temperatures of -10...2°C, stem heating or a valve neck extension is recommended. The permitted medium temperature may depend on the actuator type.
Permitted mounting position ranges from vertical to horizontal relative to the axis; mounting with the axis pointing downwards is not permitted. Observe the flow direction indicated by the arrow on the body.
-
Brand
-
ReferenceR3020-4-S2
-
EAN137630498107658
-
Kvs4 m³/h
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern3-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteFor medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
-
Differential pressure∆pmax 350 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Flow characteristicA – AB: equal-percentage; B – AB: linear
-
Permissible leakageA – AB: bubble-tight, leakage class A; B – AB: leakage class I, 1...2% of Kvs value
-
Pipe connectionInternal thread
Over 20 years of experience
Reliable service and customer trust
Help with selecting and operating equipment