Belimo R3020-4-S2 - 3-way ball control valve

Price: zł534.53
VAT included
zł434.58 tax excluded

Belimo R3020-4-S2 is a 3-way control valve with a regulating orifice for closed water systems. DN 20, PN 40, Rp 3/4" female thread and Kvs 4 m³/h.

Designed to regulate flow on the water side of ventilation and heating systems. Medium: water or water with max. 50% vol. glycol; medium temperature -10...120°C [14...248°F].

Product availability: Delivery in approx. 14 days
Share

Belimo R3020-4-S2 – 3-way control valve

A valve with a regulating orifice for closed water systems, designed for water-side control in ventilation and heating systems. Control is provided by a rotary actuator operated by a modulating or 3-point signal.

Key features and parameters

  • Pattern: 3-way; DN 20; PN 40.
  • Connection: Rp 3/4" female thread.
  • Kvs: 4 m³/h; flow through bypass B – AB: 70% of the Kvs value.
  • Medium: water, water with max. 50% vol. glycol.
  • Medium temperature: -10...120°C [14...248°F].
  • Differential pressure: ∆pmax 350 kPa; closing pressure: 1400 kPa. 200 kPa is specified for quiet operation.
  • Flow characteristic: A – AB equal percentage, B – AB linear.
  • Leakage: A – AB bubble-tight, leakage class A; B – AB leakage class I, 1...2% of the Kvs value.
  • Nickel-plated brass body; stainless steel closing element and stem.
  • Rotation angle: 90°.

For medium temperatures of -10...2°C, stem heating or a valve neck extension is recommended. The permitted medium temperature may depend on the actuator type.

Permitted mounting position ranges from vertical to horizontal relative to the axis; mounting with the axis pointing downwards is not permitted. Observe the flow direction indicated by the arrow on the body.

  • Brand
  • Reference
    R3020-4-S2
  • EAN13
    7630498107658

  • Kvs
    4 m³/h
  • Medium
    Water, water with up to 50% vol. glycol.
  • Pattern
    3-way
  • Fluid temperature
    -10...120°C [14...248°F]
  • Fluid temperature, note
    For medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
  • Differential pressure
    ∆pmax 350 kPa
  • Closing pressure
    1400 kPa
  • Differential pressure note
    200 kPa for quiet operation
  • Flow characteristic
    A – AB: equal-percentage; B – AB: linear
  • Permissible leakage
    A – AB: bubble-tight, leakage class A; B – AB: leakage class I, 1...2% of Kvs value
  • Pipe connection
    Internal thread

Techniczna karta katalogowa

Download (1.2MB)

Instrukcja montażu

Download (544.37KB)

Techniczna karta katalogowa – R3..xx-S..

Download (1.2MB)

EU Declaration of Conformity – R20.. / R30.. DN 15...32

Download (130.94KB)

Environmental Declaration – R3..

Download (70.3KB)
In business since 2005
Over 20 years of experience
A trusted partner
Reliable service and customer trust
Technical support
Help with selecting and operating equipment

You might also like

Comments (0)

No customer reviews for the moment.

4 other products in the same category

Loading...
Back to top