Belimo R3025-10-S2 - 3-way characterised control ball valve
Belimo R3025-10-S2 is a 3-way control valve with a characterised disc for closed-loop water systems. It has an Rp 1" female threaded connection, DN 25, PN 40 and Kvs 10 m³/h.
Designed to control flow on the water side of ventilation and heating systems. Suitable for water and water with a maximum of 50% vol. glycol at a medium temperature of -10...120°C [14...248°F].
Belimo R3025-10-S2 – 3-way control valve
Valve with a characterised disc for closed-loop water systems, designed for control on the water side of ventilation and heating systems. The body is made of nickel-plated brass.
Key features and specifications
- Pattern: 3-way; DN 25, PN 40.
- Pipe connection: Rp 1" female thread, in accordance with ISO 7-1.
- Kvs: 10 m³/h.
- Medium: water, water with a maximum of 50% vol. glycol.
- Medium temperature: -10...120°C [14...248°F].
- Differential pressure: ∆pmax 350 kPa; closing pressure: 1400 kPa. For quiet operation, 200 kPa is specified.
- Flow characteristic: A – AB – equal percentage; B – AB – linear.
- Permissible leakage: A – AB – bubble-tight, leakage class A; B – AB – leakage class I, 1...2% of the Kvs value.
- Angle of rotation: 90°; operating range A – AB: 15...90°, B – AB: 15...70°.
- Closing element and stem: stainless steel; characterised disc for DN 25: ETFE.
Installation notes: Permissible installation position: from vertical to horizontal relative to the axis; installation with the axis pointing downwards is not permitted. At a medium temperature of -10...2°C, stem heating or a valve neck extension is recommended. The permissible medium temperature may depend on the actuator used.
-
Brand
-
ReferenceR3025-10-S2
-
EAN137630498107726
-
Kvs10 m³/h
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern3-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteFor medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
-
Differential pressure∆pmax 350 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Flow characteristicA – AB: equal-percentage; B – AB: linear
-
Permissible leakageA – AB: bubble-tight, leakage class A; B – AB: leakage class I, 1...2% of Kvs value
-
Pipe connectionInternal thread