Belimo R3040-25-S4 - 3-way characterised control ball valve
3-way characterised control ball valve for closed water systems. DN 40, Rp 1 1/2" female thread, PN 25, Kvs 25 m³/h.
Designed for water-side control in ventilation and heating systems. Medium temperature: -10...120°C [14...248°F].
Belimo R3040-25-S4 – 3-way control valve
Valve with characterised disc for closed water systems, designed for water-side control in ventilation and heating systems.
Key technical data
- Type: 3-way; DN 40; PN 25; ps 1600 kPa.
- Connection: Rp 1 1/2" female thread.
- Kvs: 25 m³/h; flow through bypass B – AB: 70% of the Kvs value.
- Medium: water, water with max. 50% by volume glycol.
- Medium temperature: -10...120°C [14...248°F].
- Maximum differential pressure ∆pmax: 350 kPa; closing pressure: 1400 kPa. Differential pressure recommendation: 200 kPa to ensure quiet operation.
- Flow characteristic: A – AB equal percentage, B – AB linear.
- Leakage: A – AB bubble-tight, leakage class A; B – AB leakage class I, 1...2% of the Kvs value.
- Angle of rotation: 90°. Operating range A – AB: 15...90°, B – AB: 15...70°.
- Body: nickel-plated brass; closing element and stem: stainless steel.
Installation notes
Installation is permitted from vertical to horizontal; do not install with the stem pointing downwards. Observe the flow direction indicated by the arrow on the body.
At a medium temperature of -10...2°C, stem heating or a valve neck extension is recommended. The permitted medium temperature may depend on the actuator type; limitations are given in the relevant actuator data sheets.
-
Brand
-
ReferenceR3040-25-S4
-
EAN137630498107832
-
Kvs25 m³/h
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern3-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteFor medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
-
Differential pressure∆pmax 350 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Flow characteristicA – AB: equal-percentage; B – AB: linear
-
Permissible leakageA – AB: bubble-tight, leakage class A; B – AB: leakage class I, 1...2% of Kvs value
-
Pipe connectionInternal thread