Belimo R7032R-B3 - 3-way changeover ball valve DN 32
Belimo R7032R-B3 3-way changeover ball valve with PN 6 flange connection. DN 32, Kvs 32 m³/h, medium temperature -10...100°C [14...212°F].
Designed for closed water systems; supports changeover functions and open/close control on the water side of ventilation and heating systems.
Belimo R7032R-B3 – changeover ball valve
3-way valve with flange connection, designed for closed water systems. Medium: water or water with up to 50% vol. glycol.
Key technical data
- DN 32, PN 6, Kvs 32 m³/h.
- Medium temperature: -10...100°C [14...212°F].
- Differential pressure: ∆pmax 100 kPa; closing pressure: 600 kPa.
- Flow through bypass B – AB: approx. 50% of the Kvs value.
- Tightness A – AB: bubble-tight, leakage class A (EN 12266-1); B – AB: leakage class I (EN 1349 and EN 60534-4), max. 1% of the Kvs value.
- Angle of rotation: 90°; flange connection according to EN 1092-1/4.
- Nickel-plated brass body; chromium-plated brass closure element; aluminium flange.
Installation instructions
Permitted installation position: from vertical to horizontal relative to the valve axis; installation with the axis pointing downwards is not permitted. At a medium temperature of -10...2°C, heating the spindle or using a valve neck extension is recommended. The permitted medium temperature may depend on the actuator type.
-
Brand
-
ReferenceR7032R-B3
-
EAN137630498108778
-
Kvs32 m³/h
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern3-way
-
Fluid temperature-10...100°C [14...212°F]
-
Fluid temperature, noteFor medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
-
Differential pressure∆pmax 100 kPa
-
Closing pressure600 kPa
-
Permissible leakageA – AB: bubble-tight, leakage class A; B – AB: leakage class I, max. 1% of Kvs value
-
Pipe connectionFlange
Over 20 years of experience
Reliable service and customer trust
Help with selecting and operating equipment