Belimo BF230-C134 - spring-return actuator for fire dampers
Spring-return actuator for fire and smoke control dampers in ventilation and air-conditioning systems. AC 230 V supply, Close/Open control, motor and safety function torque of 20 Nm, and 12x12 mm mechanical connection.
Motor running time is <60 s / 90°, and safety function running time is <30 s @ 20°C. The actuator has 2x SPDT and IP54 protection rating.
Belimo BF230-C134
Spring-return actuator for 90° fire and smoke control dampers in ventilation and air-conditioning systems. During operation, the actuator moves the damper to its operating position and tensions the return spring. If the power supply is interrupted, the spring moves the damper to its safety position.
Key specifications
- Rated voltage: AC 230 V; voltage range: AC 198...264 V; frequency: 50/60 Hz.
- Control: Close/Open.
- Motor torque: 20 Nm; safety function torque: 20 Nm (see service life).
- Motor running time: <60 s / 90°; safety function running time: <30 s @ 20°C.
- Rotation angle: max. 95°.
- Auxiliary switches: 2x SPDT; switching points: 5° / 80°.
- Mechanical connection: form-fit connection 12x12 mm, non-through hollow shaft.
- Power consumption during operation: 8 W; at rest: 3 W; sizing power: 12.5 VA.
- Power and control connection: 1 m cable, 2x 0.75 mm², halogen-free; auxiliary switch connection: 1 m cable, 6x 0.75 mm², halogen-free.
- Protection rating: IP54.
The motor direction can be selected by L/R mounting. The actuator has manual override with a stop and a mechanical position indicator.
The actuator is adapted and mounted on the damper by the damper manufacturer; in accordance with the technical data sheet, it is supplied directly to manufacturers of safety dampers.
-
Brand
-
ReferenceBF230-C134
-
EAN137630498118531
-
AC/DC voltageAC 230 V
-
Auxiliary switch connectionCable 1 m, 6x 0.75 mm², FRNC (halogen-free)
-
Power consumption (running)8 W
-
Power consumption (holding)3 W
-
Rated power12.5 VA
-
Power supply control connection1 m cable, 2x 0.75 mm², FRNC (halogen-free)
-
Control typeClose/Open
-
Protection ratingIP54
-
Manual overrideWith stop
-
Running time (motor)<60 s / 90°
-
Running time (safety function)<30 s
-
Auxiliary contacts2x SPDT
-
Torque20 Nm
-
Direction of movement - motorSelectable by mounting L/R
-
Rotational angle95°
-
Mechanical connectionForm-fit connection 12x12 mm, blind hollow shaft
Over 20 years of experience
Reliable service and customer trust
Help with selecting and operating equipment