Belimo R2015-P4-S1 - 2-way control valve with orifice
Belimo R2015-P4-S1 is a 2-way control valve with orifice, DN 15, PN 40, with Rp 1/2" female thread and Kvs 0.4 m³/h. Designed for water-side control in ventilation and heating systems.
Medium: water or water with up to 50% by volume glycol. Medium temperature: -10...120°C [14...248°F].
Belimo R2015-P4-S1 – 2-way control valve
Control valve with regulating orifice for open and closed water systems. Designed for water-side control in ventilation and heating systems.
Key technical data
- DN 15, PN 40; Rp 1/2" female thread.
- Kvs 0.4 m³/h; equal-percentage characteristic, optimised in the opening range.
- Medium: water, water with up to 50% by volume glycol; medium temperature -10...120°C [14...248°F].
- Maximum differential pressure Δpmax 350 kPa; closing pressure ∆ps 1400 kPa. For quiet operation: 200 kPa.
- Tightness: bubble-tight, leakage rate class A (EN 12266-1).
- Rotation angle 90°; operating range 15...90°.
- Nickel-plated brass body; stainless steel closing element and spindle, regulating orifice made of ETFE.
Installation instructions
Installation is permitted from vertical to horizontal relative to the axis; do not install with the axis pointing downwards. Observe the flow direction indicated by the arrow on the body.
At a medium temperature of -10...2°C, spindle heating or an extended valve neck is recommended. The permissible medium temperature may depend on the actuator used; see its product data sheet for limitations.
-
Brand
-
ReferenceR2015-P4-S1
-
EAN137630498105258
-
Kvs0.4 m³/h
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern2-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteFor medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
-
Differential pressure∆pmax 350 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Flow characteristicEqual-percentage characteristic
-
Permissible leakageBubble-tight, leakage class A
-