Belimo R3032-S3 - 3-way changeover ball valve
Belimo R3032-S3 is a 3-way changeover ball valve, DN 32, with Rp 1 1/4" female thread. Specifications: PN 25, ps 1600 kPa, Kvs 32 m³/h and fluid temperature -10...120°C [14...248°F].
Designed for closed-loop water systems, for changeover and open/close control on the water side of ventilation and heating systems.
Belimo R3032-S3 – changeover ball valve
3-way ball valve with female thread, designed for closed-loop water systems. The valve is operated by a rotary actuator controlled by an open/close signal.
Key features
- Size DN 32; Rp 1 1/4" connection, female thread in accordance with ISO 7-1.
- PN 25; ps 1600 kPa; Kvs 32 m³/h.
- Fluid: water or water with a maximum of 50% vol. glycol; fluid temperature -10...120°C [14...248°F].
- Maximum differential pressure Δpmax 1000 kPa; closing pressure ∆ps 1400 kPa. For quiet operation: 200 kPa.
- Flow through bypass B – AB: approx. 50% of the Kvs value.
- Leakage A – AB: bubble-tight, leakage class A; B – AB: leakage class I, max. 1% of the Kvs value.
- Rotation angle: 90°.
- Nickel-plated brass body; stainless steel closure element and stem; stem seal: EPDM O-ring; seat: PTFE, EPDM O-ring.
Installation notes
Installation is permitted from the vertical to the horizontal position relative to the valve axis; installation with the axis pointing downwards is not permitted. Observe the flow direction indicated by the arrow on the body.
At a fluid temperature of -10...2°C, stem heating or a valve neck extension is recommended. The permitted fluid temperature may be limited depending on the actuator type; restrictions are specified in the relevant actuator data sheets.
-
Brand
-
ReferenceR3032-S3
-
EAN137630498107818
-
Kvs32 m³/h
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern3-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteFor medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
-
Differential pressure∆pmax 1000 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Permissible leakageA – AB: bubble-tight, leakage class A; B – AB: leakage class I, max. 1% of Kvs value
-
Pipe connectionInternal thread