Belimo R3050-58-S4 - 3-way control ball valve
Belimo R3050-58-S4 is a 3-way control valve with a regulating insert, designed for closed water systems. It has an Rp 2" female threaded connection, DN 50, PN 25 and Kvs 58 m³/h.
It handles water and water with a maximum of 50% vol. glycol at a fluid temperature of -10...120°C [14...248°F].
Belimo R3050-58-S4 – 3-way control valve
A control valve with a regulating insert for controlling flow on the water side of ventilation and heating systems. Designed for closed water systems.
Key parameters
- Pattern: 3-way; DN 50, PN 25.
- Pipe connection: Rp 2" female thread.
- Kvs: 58 m³/h; flow through bypass B – AB: 70% of the Kvs value.
- Fluid: water, water with a maximum of 50% vol. glycol.
- Fluid temperature: -10...120°C [14...248°F].
- Differential pressure: ∆pmax 350 kPa; closing pressure: 1400 kPa.
- Flow characteristic: A – AB equal-percentage, B – AB linear.
- Permissible leakage: A – AB bubble-tight, leakage class A; B – AB leakage class I, 1...2% of the Kvs value.
- Body: nickel-plated brass; closing element and stem: stainless steel.
- Rotary angle: 90°.
At a fluid temperature of -10...2°C, stem heating or a valve neck extension is recommended. The permissible fluid temperature may depend on the actuator type.
Permissible mounting position: from vertical to horizontal relative to the axis; mounting with the axis pointing downwards is not permitted. A differential pressure of 200 kPa is specified for quiet operation.
-
Brand
-
ReferenceR3050-58-S4
-
EAN137630498107894
-
Kvs58 m³/h
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern3-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteFor medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
-
Differential pressure∆pmax 350 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Flow characteristicA – AB: equal-percentage; B – AB: linear
-
Permissible leakageA – AB: bubble-tight, leakage class A; B – AB: leakage class I, 1...2% of Kvs value
-
Pipe connectionInternal thread
Over 20 years of experience
Reliable service and customer trust
Help with selecting and operating equipment