Belimo R6025R-B2 - 2-way Open/Close ball valve

Price: zł1,024.09
VAT included
zł832.59 tax excluded

Belimo R6025R-B2 is a 2-way Open/Close ball valve with flange connection, DN 25, PN 6 and Kvs 26 m³/h. Designed for shut-off functions on the water side of heating and ventilation systems.

Medium temperature: -10...100°C [14...212°F]. Differential pressure Δpmax 100 kPa; closing pressure 600 kPa.

Product availability: Delivery in approx. 14 days
Share

Belimo R6025R-B2 – technical data

2-way Open/Close ball valve for open and closed water systems. It is used for shut-off functions on the water side and Open/Close control in ventilation and heating systems.

  • Nominal diameter: DN 25; nominal pressure: PN 6.
  • Pipe connection: flange; Kvs 26 m³/h.
  • Medium: water, water with max. 50% vol. glycol.
  • Medium temperature: -10...100°C [14...212°F].
  • Differential pressure: Δpmax 100 kPa; closing pressure: 600 kPa.
  • Tightness: bubble-tight, leakage rate A (EN 12266-1).
  • Rotation angle: 90°. The valve opens by turning anticlockwise and closes by turning clockwise.
  • Body: nickel-plated brass; closing element: chrome-plated brass; flange: aluminium.

Installation notes

Permitted installation position: from vertical to horizontal relative to the valve axis. Installation with the axis pointing downwards is not permitted. Observe the direction of flow indicated by the arrow on the body.

For a medium temperature of -10...2°C, heating the shaft or using a valve neck extension is recommended. The permitted medium temperature range may depend on the actuator type; limitations are specified in the actuator data sheets.

  • Brand
  • Reference
    R6025R-B2
  • EAN13
    7630498108563

  • Kvs
    26 m³/h
  • Medium
    Water, water with up to 50% vol. glycol.
  • Pattern
    2-way
  • Fluid temperature
    -10...100°C [14...212°F]
  • Fluid temperature, note
    For medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
  • Differential pressure
    ∆pmax 100 kPa
  • Closing pressure
    600 kPa
  • Permissible leakage
    Bubble-tight, leakage class A
  • Pipe connection
    Flange

Techniczna karta katalogowa

Download (1.18MB)

Instrukcja montażu

Download (507.05KB)

Techniczna karta katalogowa – R6..R-B..

Download (1.18MB)

EU Declaration of Conformity – R20.., R30.., R60..R.., R70..R.., DN15...50

Download (64.14KB)

Environmental Declaration – R6.. DN15-50

Download (70.21KB)
In business since 2005
Over 20 years of experience
A trusted partner
Reliable service and customer trust
Technical support
Help with selecting and operating equipment

You might also like

Comments (0)

No customer reviews for the moment.

4 other products in the same category

Loading...
Back to top