Belimo EP025R2+KBAC - 2-way EPIV control valve
2-way EPIV control valve with sensor-based, pressure-independent flow control and safety function. DN 25, PN 25, Rp 1", G 1 1/4" connections and V'nom 0.97 l/s (3.5 m³/h).
AC/DC 24 V supply; BACnet MS/TP, Modbus RTU and MP-Bus communication. The valve measures fluid temperature and monitors glycol concentration.
Belimo EP025R2+KBAC – DN 25 EPIV valve
2-way control valve with sensor-based flow control and safety function, designed for closed water systems. It is used for modulating control of the water side of ventilation and heating systems.
Main features and specifications
- DN 25, PN 25; Rp 1" female and G 1 1/4" male threads.
- Nominal flow V'nom 0.97 l/s (3.5 m³/h); V'max adjustable from 25...100% V'nom.
- Fluid: water or water with max. 60% vol. glycol; fluid temperature -10...120°C [14...248°F].
- Maximum differential pressure ∆pmax 350 kPa; closing pressure ∆ps 1400 kPa.
- AC/DC 24 V supply; power consumption 4 W during operation and 3.7 W in the idle position.
- Modulating, communicative or hybrid control; operating range Y 2...10 V. BACnet MS/TP, Modbus RTU and MP-Bus communication.
- Safety function with NC/NO or 0...100% position setting; operating time 35 s / 90°.
- Ultrasonic flow measurement, fluid temperature measurement and glycol concentration monitoring.
- Configuration via NFC using Belimo Assistant 2; manual override by button.
- Electrical connection: 1 m cable; IEC/EN IP54 degree of protection; IEC/EN protection class III, Protective Extra-Low Voltage (PELV).
Z-INSH15 insulation shell is included; according to the documentation, it is not supplied in the Asia Pacific region. For fluid temperatures of -10...2°C, shaft heating or a valve neck extension is recommended.
-
Brand
-
ReferenceEP025R2+KBAC
-
EAN137630498111129
-
MediumWater, water with max. 60% vol. glycol.
-
Pattern2-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteAt a medium temperature of -10...2°C, heating the shaft or extending the valve neck is recommended.
-
Differential pressure∆pmax 350 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Flow characteristicEqual-percentage characteristic
-
Permissible leakageBubble-tight, leakage class A
-
Pipe connectionInternal and external thread
-
V'nom [l/s]0.97
-
Adjustable flow rate25...100% V'nom
Over 20 years of experience
Reliable service and customer trust