Belimo EP032R2+KBAC - 2-way EPIV control valve DN 32
Belimo EP032R2+KBAC is a 2-way EPIV control valve with pressure-independent flow control and a safety function. The DN 32, PN 25 model has Rp 1 1/4" female and G 1 1/2" male threaded connections, and V'nom 1.67 l/s (6 m³/h).
AC/DC 24 V power supply; BACnet MS/TP, Modbus RTU and MP-Bus communication. The device measures fluid flow and temperature and monitors glycol concentration.
Belimo EP032R2+KBAC – EPIV valve
2-way control valve with a flow sensor and actuator with a safety function, designed for closed water systems and water-side control in ventilation and heating systems. If the power supply is interrupted, the actuator moves the valve to the selected safety position using energy stored in capacitors.
Key features and parameters
- DN 32, PN 25; Rp 1 1/4" female and G 1 1/2" male threads.
- V'nom 1.67 l/s (6 m³/h); V'max adjustable from 25...100% V'nom.
- Fluid: water or water with a maximum of 60% vol. glycol; fluid temperature -10...120°C [14...248°F].
- Maximum differential pressure ∆pmax 350 kPa; closing pressure ∆ps 1400 kPa.
- AC/DC 24 V power supply; power consumption during operation 5 W, in standby position 3.9 W; wire sizing power 7.5 VA.
- Modulating, communicative or hybrid control; control signal Y range 2...10 V; BACnet MS/TP, Modbus RTU and MP-Bus communication.
- Ultrasonic flow measurement, fluid temperature measurement and glycol concentration monitoring.
- Safety position NC/NO or adjustable from 0...100%; safety mode positioning time 35 s / 90°.
- NFC interface for configuration with Belimo Assistant 2; manual adjustment by button.
- 1 m connecting cable; IEC/EN IP54 degree of protection.
Z-INSH32 insulation shell is specified as included; according to the datasheet, it is not included in the Asia-Pacific region.
-
Brand
-
ReferenceEP032R2+KBAC
-
EAN137630498111143
-
MediumWater, water with max. 60% vol. glycol.
-
Pattern2-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteAt a medium temperature of -10...2°C, heating the shaft or extending the valve neck is recommended.
-
Differential pressure∆pmax 350 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Flow characteristicEqual-percentage characteristic
-
Permissible leakageBubble-tight, leakage class A
-
Pipe connectionInternal and external thread
-
V'nom [l/s]1.67
-
Adjustable flow rate25...100% V'nom
Over 20 years of experience
Reliable service and customer trust
Help with selecting and operating equipment