Belimo EP040R2+KBAC - DN 40 2-way EPIV control valve

Price: zł3,856.41
VAT included
zł3,135.29 tax excluded

2-way EPIV control valve with pressure-independent flow control and safety function. DN 40, PN 25, Rp 1 1/2" and G 2" connections, V'nom 2.78 l/s.

AC/DC 24 V supply; analogue or communication-based control via BACnet MS/TP, Modbus RTU and MP-Bus. The valve measures fluid flow and temperature and monitors glycol concentration.

Product availability: Delivery in approx. 14 days
Share

Belimo EP040R2+KBAC – DN 40 EPIV valve

2-way control valve with flow sensor and actuator with safety function. Designed for closed water systems and modulating control of ventilation and heating systems on the water side. If the power supply fails, stored electrical energy moves the valve to the selected safety position.

Key features and specifications

  • DN 40, PN 25; Rp 1 1/2" female thread and G 2" male thread.
  • V'nom 2.78 l/s (10 m³/h); V'max setting range 25...100% V'nom.
  • AC/DC 24 V supply; power consumption 5 W during operation and 3.9 W at rest.
  • Modulating, communication-based and hybrid control; Y 2...10 V control signal and BACnet MS/TP, Modbus RTU and MP-Bus communication.
  • Ultrasonic flow measurement, fluid temperature measurement and glycol concentration monitoring.
  • Fluid: water or water with up to 60% vol. glycol; fluid temperature -10...120°C [14...248°F].
  • ∆pmax 350 kPa; closing pressure ∆ps 1400 kPa.
  • NC/NO safety position or adjustable within 0...100%; safety function travel time 35 s / 90°.
  • Manual override by push-button; configuration via NFC using Belimo Assistant 2.
  • 1 m connection cable; IEC/EN IP54 degree of protection.

Documentation for DN 40 specifies the Z-INSH32 insulation shell as an included component, except that it is not included in the Asia-Pacific region.

  • Brand
  • Reference
    EP040R2+KBAC
  • EAN13
    7630498111167

  • Medium
    Water, water with max. 60% vol. glycol.
  • Pattern
    2-way
  • Fluid temperature
    -10...120°C [14...248°F]
  • Fluid temperature, note
    At a medium temperature of -10...2°C, heating the shaft or extending the valve neck is recommended.
  • Differential pressure
    ∆pmax 350 kPa
  • Closing pressure
    1400 kPa
  • Differential pressure note
    200 kPa for quiet operation
  • Flow characteristic
    Equal-percentage characteristic
  • Permissible leakage
    Bubble-tight, leakage class A
  • Pipe connection
    Internal and external thread
  • V'nom [l/s]
    2.78
  • Adjustable flow rate
    25...100% V'nom

Techniczna karta katalogowa

Download (4.98MB)

Instrukcja montażu

Download (948.42KB)

Techniczna karta katalogowa – EP..R2+KBAC

Download (4.98MB)

EU Declaration of Conformity – EP040R2+KBAC

Download (307.34KB)

Environmental Declaration – EP..R2..+KBAC

Download (72.95KB)