Belimo R3015-P63-S1 - 3-way control valve with characterized plug
Belimo R3015-P63-S1 is a 3-way control valve with a characterized plug for closed water systems. DN 15, Rp 1/2" female thread, PN 40, Kvs 0.63 m³/h.
Designed to control flow on the water side of ventilation and heating systems. Medium: water or water with a maximum of 50% by volume glycol; medium temperature -10...120°C [14...248°F].
Belimo R3015-P63-S1 – 3-way control valve
A valve with a characterized plug, designed for closed water systems and water-side control in ventilation and heating systems. The body is made of nickel-plated brass.
Key features and specifications
- Design: 3-way; DN 15, PN 40.
- Connection: Rp 1/2" female thread.
- Kvs: 0.63 m³/h; flow through bypass B – AB: 70% of the Kvs value.
- Medium: water, water with a maximum of 50% by volume glycol.
- Medium temperature: -10...120°C [14...248°F].
- Differential pressure: ∆pmax 350 kPa; closing pressure: 1400 kPa. 200 kPa is specified to ensure quiet operation.
- Flow characteristic: A – AB equal-percentage, B – AB linear.
- Leakage: A – AB bubble-tight, leakage class A; B – AB leakage class I, 1...2% of the Kvs value.
- Angle of rotation: 90°; operating range A – AB: 15...90°, B – AB: 15...70°.
Installation notes
Permitted mounting position: from vertical to horizontal relative to the valve axis; installation with the axis pointing downwards is not permitted. Observe the flow direction indicated by the arrow on the body.
At a medium temperature of -10...2°C, heating the valve stem or using a valve neck extension is recommended. The permitted medium temperature may depend on the actuator used; restrictions are specified in the relevant actuator data sheets.
-
Brand
-
ReferenceR3015-P63-S1
-
EAN137630498107481
-
Kvs0.63 m³/h
-
MediumWater, water with up to 50% vol. glycol.
-
Pattern3-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteFor medium temperatures of -10...2°C, heating the shaft or extending the valve neck is recommended. The permissible medium temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for restrictions.
-
Differential pressure∆pmax 350 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Flow characteristicA – AB: equal-percentage; B – AB: linear
-
Permissible leakageA – AB: bubble-tight, leakage class A; B – AB: leakage class I, 1...2% of Kvs value
-
Pipe connectionInternal thread
Over 20 years of experience
Reliable service and customer trust
Help with selecting and operating equipment