Belimo EP050R2+KBAC - 2-way EPIV control valve DN 50
2-way EPIV control valve with pressure-independent flow control and safety function. DN 50, PN 25, Rp 2" female and G 2 1/2" male threaded connections, V'nom 4.17 l/s (15 m³/h).
AC/DC 24 V supply; modulating, communicative or hybrid control via BACnet MS/TP, Modbus RTU and MP-Bus. The valve measures flow and fluid temperature and monitors glycol concentration.
Belimo EP050R2+KBAC – EPIV control valve
2-way control valve with sensor-based flow measurement and control, independent of differential pressure. It is designed for closed-loop water systems and modulating control of the water-side circuits of ventilation and heating systems. If the power supply fails, energy stored in the capacitors moves the valve to the selected safety position.
Key features and specifications
- Size DN 50, PN 25; Rp 2" female and G 2 1/2" male threads.
- Nominal flow V'nom 4.17 l/s (15 m³/h); V'max setting range 25...100% V'nom.
- AC/DC 24 V supply; power consumption 5 W during operation and 3.9 W in standby.
- Modulating, communicative and hybrid control; BACnet MS/TP, Modbus RTU, MP-Bus communication. Y signal operating range: 2...10 V.
- Ultrasonic flow measurement, fluid temperature measurement and glycol concentration monitoring.
- Medium: water or water with up to 60% vol. glycol; fluid temperature -10...120°C [14...248°F].
- Maximum differential pressure ∆pmax 350 kPa; closing pressure ∆ps 1400 kPa.
- Safety position NC/NO or adjustable within 0...100%; safety mode repositioning time 35 s / 90°.
- NFC interface for configuration using Belimo Assistant 2; manual repositioning by button.
- Electrical connection: 1 m cable, 6x 0.75 mm²; IEC/EN IP54 protection rating.
The documentation lists an insulation shell for DN 32...50 as a set component, noting that it is not included in the Asia-Pacific region.
-
Brand
-
ReferenceEP050R2+KBAC
-
EAN137630498111181
-
MediumWater, water with max. 60% vol. glycol.
-
Pattern2-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteAt a medium temperature of -10...2°C, heating the shaft or extending the valve neck is recommended.
-
Differential pressure∆pmax 350 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Flow characteristicEqual-percentage characteristic
-
Permissible leakageBubble-tight, leakage class A
-
Pipe connectionInternal and external thread
-
V'nom [l/s]4.17
-
Adjustable flow rate25...100% V'nom