Belimo EP080F2-25+BAC - 2-way EPIV control valve
2-way, flanged EPIV control valve with pressure-independent flow and flow measurement-based control. DN 80, PN 25, V'nom 11.7 l/s (42 m³/h). AC/DC 24 V supply.
Supports BACnet MS/TP, Modbus RTU and MP-Bus, as well as a 2...10 V control signal. Enables glycol concentration monitoring and NFC configuration using Belimo Assistant 2.
Belimo EP080F2-25+BAC
Flanged, 2-way EPIV control valve with electronic pressure-independent flow control. The sensor measures the flow, and the actuator adjusts the valve position to match the setpoint. The product is designed for closed water systems and water-side control in ventilation and heating systems.
Key features and specifications
- DN 80, PN 25; flange connection in accordance with EN 1092-2.
- V'nom 11.7 l/s (700 l/min; 42 m³/h); V'max setting range 25...100% V'nom.
- ∆pmax 350 kPa; closing pressure ∆ps 690 kPa.
- AC/DC 24 V supply; power consumption during operation 3.3 W, at rest 2.4 W; sizing value for cable selection 6.2 VA.
- Modulating, communicative or hybrid control; control signal Y range 2...10 V; BACnet MS/TP, Modbus RTU and MP-Bus communication.
- Medium: water or water with a maximum of 60% vol. glycol; medium temperature -10...120°C [14...248°F].
- Ultrasonic flow measurement, medium temperature measurement and glycol concentration monitoring in the 0...60% range.
- NFC configuration using Belimo Assistant 2; manual adjustment by button, with the option to lock it.
- IEC/EN IP54 degree of protection; IEC/EN protection class III, Protective Extra-Low Voltage (PELV).
At a medium temperature of -10...2°C, extending the valve neck is recommended. The permitted medium temperature may depend on the actuator type.
-
Brand
-
ReferenceEP080F2-25+BAC
-
EAN137630498136832
-
MediumWater, water with max. 60% vol. glycol.
-
Pattern2-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteAt a fluid temperature of -10...2°C, extending the valve neck is recommended. The permissible fluid temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for limitations.
-
Differential pressure∆pmax 350 kPa
-
Closing pressure690 kPa
-
Differential pressure note200 kPa for quiet operation
-
Flow characteristicEqual-percentage characteristic
-
Permissible leakageBubble-tight, leakage class A
-
Pipe connectionFlange
-
V'nom [l/s]11.7
-
Adjustable flow rate25...100% V'nom
Over 20 years of experience
Reliable service and customer trust
Help with selecting and operating equipment