Belimo EP100F2-25+KBAC - 2-way pressure-independent control valve

Price: zł42,625.65
VAT included
zł34,655.00 tax excluded

2-way EPIV control valve with sensor-based flow control and fail-safe function. DN 100, PN 25 version with flanged connection; V'nom 20.8 l/s (75 m³/h).

AC/DC 24 V supply. 2...10 V analogue control and BACnet MS/TP, Modbus RTU and MP-Bus communication. The device measures fluid temperature and monitors glycol concentration.

Product availability: Product unavailable
Share

Notify me when available

Interested in this product? Drop us an email and we will let you know when it's available for order.

Belimo EP100F2-25+KBAC

Pressure-independent 2-way EPIV control valve with flow sensor and actuator with fail-safe function. Designed for closed water systems and modulating control of water-side ventilation and heating systems.

Key features and specifications

  • Nominal size DN 100, nominal pressure PN 25, flanged connection.
  • Nominal flow V'nom 20.8 l/s (75 m³/h); V'max setting range 25...100% V'nom.
  • Fluid: water or water with max. 60% vol. glycol; fluid temperature -10...120°C [14...250°F].
  • Differential pressure ∆pmax 350 kPa; closing pressure ∆ps 690 kPa.
  • AC/DC 24 V supply; power consumption during operation 12.1 W, in standby position 4.1 W.
  • Modulating control 2...10 V, BACnet MS/TP, Modbus RTU and MP-Bus communication, and hybrid mode.
  • Ultrasonic flow measurement, fluid temperature measurement and glycol concentration monitoring.
  • Fail-safe function with position setting 0...100%; fail-safe movement time 35 s / 90°.
  • Configuration via NFC using Belimo Assistant 2; manual override by push-button.
  • 1 m connection cable; IEC/EN IP54 degree of protection.

At fluid temperatures of -10...2°C, a valve neck extension is recommended. The permissible fluid temperature may depend on the actuator type.

  • Brand
  • Reference
    EP100F2-25+KBAC
  • EAN13
    7630498136887

  • Medium
    Water, water with max. 60% vol. glycol.
  • Pattern
    2-way
  • Fluid temperature
    -10...120°C [14...250°F]
  • Fluid temperature, note
    At a fluid temperature of -10...2°C, extending the valve neck is recommended. The permissible fluid temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for limitations.
  • Differential pressure
    ∆pmax 350 kPa
  • Closing pressure
    690 kPa
  • Differential pressure note
    200 kPa for quiet operation
  • Flow characteristic
    Equal-percentage characteristic
  • Permissible leakage
    Bubble-tight, leakage class A
  • Pipe connection
    Flange
  • V'nom [l/s]
    20.8
  • Adjustable flow rate
    25...100% V'nom

Techniczna karta katalogowa

Download (4.29MB)

Instrukcja montażu

Download (1007.6KB)

Techniczna karta katalogowa – EP..F2-25+KBAC

Download (4.26MB)

EU Declaration of Conformity – EP100F2-25+KBAC

Download (361.78KB)