Belimo EP065F2-16+KBAC - 2-way EPIV control valve
2-way EPIV control valve with pressure-independent flow, sensor-based flow control and a safety function. DN 65, PN 16, flange connection, V'nom 8.3 l/s (30 m³/h).
AC/DC 24 V power supply; modulating, communicative or hybrid control via BACnet MS/TP, Modbus RTU and MP-Bus. The device measures fluid temperature and monitors glycol concentration.
Belimo EP065F2-16+KBAC – EPIV control valve
2-way control valve with a flow sensor and safety function, designed for closed water systems and water-side control in ventilation and heating systems. If the power supply is interrupted, energy stored in the capacitors moves the valve to the selected safety position.
Key features and specifications
- DN 65, PN 16; flange connection.
- V'nom 8.3 l/s, 500 l/min, 30 m³/h; V'max adjustable from 25...100% of V'nom.
- Fluid: water or water with a maximum of 60% vol. glycol; fluid temperature -10...120°C [14...248°F].
- ∆pmax 350 kPa; closing pressure ∆ps 690 kPa.
- AC/DC 24 V power supply; power consumption during operation 8.6 W, in standby position 4.1 W.
- Control signal Y range: 2...10 V; communication via BACnet MS/TP, Modbus RTU and MP-Bus.
- Ultrasonic flow measurement, fluid temperature measurement and glycol concentration monitoring in the range 0...60%.
- Travel time to safety position: 35 s / 90°; safety position setting: NC/NO or 0...100%.
- NFC interface for configuration using Belimo Assistant 2; manual operation by button.
- IEC/EN IP54 degree of protection; IEC/EN protection class III, Protective Extra-Low Voltage (PELV).
At a fluid temperature of -10...2°C, extending the valve neck is recommended. The permissible fluid temperature may depend on the actuator type.
-
Brand
-
ReferenceEP065F2-16+KBAC
-
EAN137630498136788
-
MediumWater, water with max. 60% vol. glycol.
-
Pattern2-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteAt a fluid temperature of -10...2°C, extending the valve neck is recommended. The permissible fluid temperature may be limited depending on the actuator type. Refer to the relevant actuator data sheets for limitations.
-
Differential pressure∆pmax 350 kPa
-
Closing pressure690 kPa
-
Differential pressure note200 kPa for quiet operation
-
Flow characteristicEqual-percentage characteristic
-
Permissible leakageBubble-tight, leakage class A
-
Pipe connectionFlange
-
V'nom [l/s]8.3
-
Adjustable flow rate25...100% V'nom
Over 20 years of experience