Belimo EXT-H640P-900 - 2-way pressure-independent globe valve

Price: zł20,917.38
VAT included
zł17,006.00 tax excluded

Belimo EXT-H640P-900 2-way globe valve with flow independent of pressure changes, DN 40, PN 16, with flanged connection. V'nom is 3.00 l/s.

Designed for closed water circuits (pH >7) and district heating networks. Medium temperature: 5...140°C [41...284°F].

Product availability: Product unavailable
Share

Notify me when available

Interested in this product? Drop us an email and we will let you know when it's available for order.

Belimo EXT-H640P-900 – 2-way globe valve

Mechanical globe valve with differential pressure regulator, designed for closed water circuits (pH >7) and district heating networks. The regulator compensates for pressure fluctuations and maintains a constant differential pressure across the control valve. Correct flow regulation requires a minimum differential pressure across the valve.

Key features and parameters

  • Type: 2-way; DN 40; PN 16; flanged connection according to EN 1092-2.
  • V'nom: 3.00 l/s (11 m³/h); Kvs theor.: 20 m³/h; stroke: 13 mm; Sv min.: 23.
  • Medium: water or water with up to 30% by volume glycol; medium temperature: 5...140°C [41...284°F].
  • Maximum differential pressure across the control valve: 1000 kPa. To prevent cavitation, ∆pmax must be calculated in accordance with the design notes.
  • Flow characteristic: equal percentage; permissible leakage: max. 0.05% of the Kvs value.
  • Valve body: EN-GJL-250 (GG 25), with protective coating.
  • Maximum flow V'max can be adjusted using the setting ring on the valve neck.

Installation instructions

Installation is permitted in a vertical position with a deviation of up to ±45° relative to the stem. Observe the flow direction indicated by the arrow on the body.

  • Brand
  • Reference
    EXT-H640P-900
  • EAN13
    7630498104244

  • Medium
    Water, water with max. 30% vol. glycol.
  • Pattern
    2-way
  • Fluid temperature
    5...140°C [41...284°F]
  • Differential pressure note
    To prevent cavitation during operation, the maximum differential pressure ∆pmax must be calculated in accordance with the design notes.
  • Flow characteristic
    Equal-percentage characteristic
  • Permissible leakage
    Max. 0.05% of Kvs value
  • Pipe connection
    Flange
  • V'nom [l/s]
    3.00

Techniczna karta katalogowa

Download (1.15MB)

Techniczna karta katalogowa – EXT-H6..P..

Download (1.25MB)
In business since 2005
Over 20 years of experience
A trusted partner
Reliable service and customer trust
Technical support
Help with selecting and operating equipment

You might also like

Comments (0)

No customer reviews for the moment.

4 other products in the same category

Loading...
Back to top