Belimo EV020R2+MID - 2-way Energy Valve™ control valve DN 20
Belimo EV020R2+MID is a 2-way Energy Valve™ control valve with a thermal energy meter, certified for heating applications in accordance with MID / EN 1434. Designed for closed water systems; it enables flow or power control and monitoring of power and energy.
DN 20, PN 25, Rp 3/4" and G 1" connections, V'nom 0.69 l/s. AC/DC 24 V supply; BACnet/IP, BACnet MS/TP, Modbus TCP, Modbus RTU, MP-Bus and Cloud communication.
Belimo Energy Valve™ EV020R2+MID
2-way control valve with actuator and thermal energy meter. The device is designed for water-side control in ventilation and heating systems with a closed water circuit. The meter is MID-approved as a heat meter and complies with EN 1434.
Key features and specifications
- Size DN 20, PN 25; Rp 3/4" female and G 1" male threads.
- Nominal flow V'nom 0.69 l/s (2.5 m³/h); V'max adjustable within 25...100% V'nom.
- Control of flow, power, position or differential pressure; differential pressure control requires a sensor, which is not included.
- Ultrasonic flow measurement, power and energy monitoring, and glycol concentration monitoring; data storage for 13 months.
- AC/DC 24 V supply; power consumption during operation 4 W, in standby position 3.7 W; power consumption for cable sizing 6.5 VA.
- Control signal Y 2...10 V; modulating, communicative and hybrid modes. Communication protocols and services: BACnet/IP, BACnet MS/TP, Modbus TCP, Modbus RTU, MP-Bus, Cloud.
- NFC interface and integrated web server; configuration via Belimo Assistant 2 or the web server. Integrated delta T manager.
- Medium: water; medium temperature -10...120°C [14...248°F]. MID certification applies to the range 15...120°C.
- Differential pressure ∆pmax 350 kPa; closing pressure ∆ps 1400 kPa.
- IEC/EN IP54 degree of protection; IEC/EN protection class III, Protective Extra-Low Voltage (PELV).
- 1 m connection cable; manual adjustment by button with locking option. Z-INSH15 insulation shell included, except in the Asia-Pacific region.
At medium temperatures of -10...2°C, the manufacturer recommends shaft heating or a valve neck extension.
-
Brand
-
ReferenceEV020R2+MID
-
EAN137630498111259
-
MediumWater
-
Pattern2-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteMID certificate 15...120°C. At a fluid temperature of -10...2°C, heating the stem or extending the valve neck is recommended.
-
Differential pressure∆pmax 350 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Flow characteristicEqual-percentage characteristic
-
Permissible leakageBubble-tight, leakage class A
-
Pipe connectionInternal and external thread
-
V'nom [l/s]0.69
-
Adjustable flow rate25...100% V'nom
Over 20 years of experience
Reliable service and customer trust
Help with selecting and operating equipment