Belimo EV032R2+MID - 2-way Energy Valve with thermal energy meter
Belimo EV032R2+MID is a 2-way Energy Valve control valve with a thermal energy meter, MID-certified for heating applications and compliant with EN 1434. The DN 32, PN 25 version has Rp 1 1/4" female and G 1 1/2" male threaded connections and V'nom 1.67 l/s.
The device enables flow or power control based on measurement, as well as power and energy monitoring. It supports BACnet/IP, BACnet MS/TP, Modbus TCP, Modbus RTU, MP-Bus and Cloud.
Belimo EV032R2+MID – Energy Valve DN 32
2-way control valve with actuator and thermal energy meter for closed water systems. The meter is MID-approved for heat measurement and complies with EN 1434. The device is designed for water-side control in ventilation and heating systems.
Key features and specifications
- DN 32, PN 25; Rp 1 1/4" female and G 1 1/2" male threaded connections.
- V'nom 1.67 l/s (6 m³/h); V'max setting: 25...100% V'nom.
- Control of flow, power, position or differential pressure; differential pressure control mode requires a sensor, which is not included.
- Ultrasonic flow measurement; monitoring of power, energy and glycol concentration.
- Integrated delta T controller and 13 months of data logging.
- AC/DC 24 V supply; power consumption 5 W during operation and 3.9 W in standby position.
- Modulating, communicative or hybrid control; Y control signal range: 2...10 V.
- Communication: BACnet/IP, BACnet MS/TP, Modbus TCP, Modbus RTU, MP-Bus, Cloud; integrated web server and NFC interface for configuration via Belimo Assistant 2.
- Medium: water; fluid temperature -10...120°C [14...248°F]. Fluid temperature range covered by MID certification: 15...120°C.
- ∆pmax 350 kPa; closing pressure ∆ps 1400 kPa.
- IEC/EN IP54 protection rating; IEC/EN protection class III, Protective Extra-Low Voltage (PELV).
- Manual adjustment using a push-button, with the option to lock it; 1 m power and control cable.
An insulation shell for DN 32...50 is provided; according to the documentation, it is not included in the Asia Pacific region.
-
Brand
-
ReferenceEV032R2+MID
-
EAN137630498111334
-
MediumWater
-
Pattern2-way
-
Fluid temperature-10...120°C [14...248°F]
-
Fluid temperature, noteMID certificate 15...120°C. At a fluid temperature of -10...2°C, heating the stem or extending the valve neck is recommended.
-
Differential pressure∆pmax 350 kPa
-
Closing pressure1400 kPa
-
Differential pressure note200 kPa for quiet operation
-
Flow characteristicEqual-percentage characteristic
-
Permissible leakageBubble-tight, leakage class A
-
Pipe connectionInternal and external thread
-
V'nom [l/s]1.67
-
Adjustable flow rate25...100% V'nom
Over 20 years of experience
Reliable service and customer trust
Help with selecting and operating equipment