Belimo EXT-H625XP-315 - 2-way pressure-independent globe valve
Belimo EXT-H625XP-315 globe valve, 2-way, with flow independent of pressure changes. DN 25 flange connection, PN 25; V'nom 0.80 l/s.
Designed for closed water circuits (pH >7) and district heating networks. Fluid temperature: 5...140°C [41...284°F].
Belimo EXT-H625XP-315
2-way globe valve with a mechanical differential pressure controller and an actuator-driven Belimo control valve. The controller compensates for pressure fluctuations and maintains a constant differential pressure across the control valve. Correct flow control requires maintaining the minimum differential pressure across the valve.
Key features
- Nominal size DN 25; flange connection in accordance with EN 1092-2; PN 25.
- V'nom 0.80 l/s; theoretical Kvs value 6.3 m³/h; stroke 11 mm.
- Fluid: water or water with a maximum of 30% vol. glycol; fluid temperature 5...140°C [41...284°F].
- Maximum differential pressure across the control valve: 1500 kPa. To prevent cavitation, ∆pmax must be calculated in accordance with the design notes.
- Flow characteristic: equal percentage; permissible leakage: max. 0,02% of the Kvs value.
- Valve body: EN-GJS-400-18-LT (GGG 40.3).
- Permissible mounting position: vertical to ±45° relative to the stem.
Maximum flow V'max can be adjusted using the setting ring on the valve neck. Maintain the flow direction indicated by the arrow on the body.
-
Brand
-
ReferenceEXT-H625XP-315
-
EAN137630498120336
-
MediumWater, water with max. 30% vol. glycol.
-
Pattern2-way
-
Fluid temperature5...140°C [41...284°F]
-
Differential pressure noteTo prevent cavitation during operation, the maximum differential pressure ∆pmax must be calculated in accordance with the design notes.
-
Flow characteristicEqual-percentage characteristic
-
Permissible leakageMax. 0.02% of Kvs value
-
Pipe connectionFlange
-
V'nom [l/s]0.80
Over 20 years of experience
Reliable service and customer trust
Help with selecting and operating equipment